Again, I never meant to discuss ships bonding and still not. Not sure why you are bringing it up, again.This is not about bonding. In order to trip the shore system, you are dealing with earth ground. Once an isolation transformer is installed, you are isolated from earth ground. The boat ground is not tied to earth/dock ground. The internal ground faults on the boat only trip relative to ground to the transformer which is the source; the only source.
Your term source is confusing. May I say it a different way?
Your transformer is the only location or only source of all ship-side electrical connects.
O K, So I understand your boat does not make a green wire connect to the dock service pole.
I also understand you believe all boats are wired this same way and there are no other options for other existing and new transformer installations.